Permit Number: T21CM04198
Parcel: 116206300

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM04198
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/06/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/11/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Drawing G0.0 shows a single drinking fountain located outside of the restrooms. Section 410.3, IPC 2018 clearly states that a minimum of two drinking fountains are required, one for people that use a wheelchair and one for standing persons. Alternatively, a drinking fountain with two spouts (one high and one low) is acceptable. [Initial comment: Provide the number of drinking fountains that complies with the requirements of Sections 2902.1 and 2902.5, IBC 2018 and Section 410.3, IPC 2018.]
08/11/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed. [Initial comment: Show that the walk-in cooler meets the construction requirements of Section C403.10.2, IECC 2018.]
2. Comment not addressed. [Initial comment: Show that the walk-in cooler meets the efficiency requirements of Section C403.10.2.1, IECC 2018.]
08/23/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved