Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM04198
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/06/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
08/11/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Drawing G0.0 shows a single drinking fountain located outside of the restrooms. Section 410.3, IPC 2018 clearly states that a minimum of two drinking fountains are required, one for people that use a wheelchair and one for standing persons. Alternatively, a drinking fountain with two spouts (one high and one low) is acceptable. [Initial comment: Provide the number of drinking fountains that complies with the requirements of Sections 2902.1 and 2902.5, IBC 2018 and Section 410.3, IPC 2018.] |
08/11/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Comment not addressed. [Initial comment: Show that the walk-in cooler meets the construction requirements of Section C403.10.2, IECC 2018.] 2. Comment not addressed. [Initial comment: Show that the walk-in cooler meets the efficiency requirements of Section C403.10.2.1, IECC 2018.] |
08/23/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |