Permit Number: T21CM04123
Parcel: 109224450

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T21CM04123
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/02/2021 STEVE SHIELDS ZONING REVIEW Approved
11/02/2021 SSHIELD1 ENGINEERING REVIEW Passed
11/23/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM04123

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


PLUMBING REVIEW COMMENTS:
Denied
1-Provide new CU installation detail. Show method of attachment to the roof structure? IMC-301.15
2-Show CU will be installed with at least 10' separation from the roof edge or provide 42" high parapet to comply with IMC304.11
3-Provide outside air for ATM Room. IMC-403.3.1.1

Final Status

Task End Date Reviewer's Name Type of Review Description
11/24/2021 VVERA1 OUT TO CUSTOMER Completed