| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/02/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 11/02/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 11/23/2021 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T21CM04123 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. PLUMBING REVIEW COMMENTS: Denied 1-Provide new CU installation detail. Show method of attachment to the roof structure? IMC-301.15 2-Show CU will be installed with at least 10' separation from the roof edge or provide 42" high parapet to comply with IMC304.11 3-Provide outside air for ATM Room. IMC-403.3.1.1 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/24/2021 | VVERA1 | OUT TO CUSTOMER | Completed |