Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM04123
Parcel: 109224450

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM04123
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/08/2021 JVINCEN1 FIRE REVIEW Approved
09/13/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Approved E1.0 GENERAL NOTES: No issues 1st review
E2.0 LIGHTING: No issues 1st review
E2.1 LIGHTING CONTROL DETAILS: No issues 1st review
Added E2.2 PHOTOMETRIC EMERGENCY LIGHTING: No electrical issues
Added E2.3 EMERGENCY LIGHT SPECS: No electrical issues
Added E2.4 PHOTOMETRICS ATM'S: Not an electrical issue, but Max lighting of 76 fc is excessive for outdoor lighting and
ruins Max/Min ratio. Would not meet typical Max/Min ratio requirements.
Added E2.5 ATM / PARKING LIGHTING SPECS: No electrical issues
E3.0 POWER PLAN: No electrical issues with revisions
E3.1 POWER PLAN: No electrical issues with revisions
E3.2 BUILDING MANAGEMENT SYSTEM: No electrical issues with revisions
E3.3 RISER DETAILS: No issues 1st review
E4.0 SINGLE LINE DIAGRAM:
Need to provide size of conductors for branch circuits. Comment addressed / no issue
Need to provide short circuit fault calculation for New panel. Comment addressed / no issue
E5.0 COMCHECK: No issues 1st review