Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM04123
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/08/2021 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 09/13/2021 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Approved | E1.0 GENERAL NOTES: No issues 1st review E2.0 LIGHTING: No issues 1st review E2.1 LIGHTING CONTROL DETAILS: No issues 1st review Added E2.2 PHOTOMETRIC EMERGENCY LIGHTING: No electrical issues Added E2.3 EMERGENCY LIGHT SPECS: No electrical issues Added E2.4 PHOTOMETRICS ATM'S: Not an electrical issue, but Max lighting of 76 fc is excessive for outdoor lighting and ruins Max/Min ratio. Would not meet typical Max/Min ratio requirements. Added E2.5 ATM / PARKING LIGHTING SPECS: No electrical issues E3.0 POWER PLAN: No electrical issues with revisions E3.1 POWER PLAN: No electrical issues with revisions E3.2 BUILDING MANAGEMENT SYSTEM: No electrical issues with revisions E3.3 RISER DETAILS: No issues 1st review E4.0 SINGLE LINE DIAGRAM: Need to provide size of conductors for branch circuits. Comment addressed / no issue Need to provide short circuit fault calculation for New panel. Comment addressed / no issue E5.0 COMCHECK: No issues 1st review |