Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T21CM04123
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/17/2021 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Plan Set references Glendale Fire. Prevention note #1 does not meet the TFD sign requirements. Sign requirements for addressing can be found on our website. Please adjust your plans and resubmit Jennifer.Peel-Davis@Tucsonaz.gov 520-837-7033 |
| 05/19/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/04/2021 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T21CM04123 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Denied 1. No structural plan review. 2. Provide existing and demolition floor plan. MECHANICAL REVIEW COMMENTS: Denied 1-Provide detail of upper/lower RTUs attachments to structure. IMC-301.15 ELECTRICAL REVIEW COMMENTS Denied E4.0 SINGLE LINE DIAGRAM: Need to provide size of conductors for branch circuits. Need to provide short circuit fault calculation for New panel PLUMBING REVIEW COMMENTS: Approved |
| 06/09/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 06/09/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 06/09/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/09/2021 | NGARCIA3 | OUT TO CUSTOMER | Completed |