Permit Number: T21CM04119
Parcel: 12218025B

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM04119
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/17/2021 JPEELDA1 FIRE REVIEW Reqs Change Plans shall indicate the type of construction, the occupancy type, the occupant load. The building is over 3,600 sq feet so we will need a letter from Tucson Water stating that it meets the IFC Apendix B requirements for type of construction
Provide location of existing hydrants to the building. we will also need to know the distance from the hydrant to the furthest part of the building as the hose lays.
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
05/19/2021 ROBERT SHERRY WATER REVIEW Completed
06/09/2021 STEVE SHIELDS ZONING REVIEW Reqs Change FROM: PDSD Zoning Review

PROJECT:
T21CM04119
1601 N Alvernon Way

TRANSMITTAL: June 9, 2021
This site is located in the O-2 zone.

1. As this is a commercial site a Development Package (DP), commercial site plan, is required to be submitted and approved prior to approval of the building plans. The DP must meet the requirements of Administrative Manual 2-06.
The DP is a separate submittal from the building plans and must be submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp.
Under “Submission Type*” “Site Review”
Until the DP is approved Zoning cannot approve the building plans.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov
06/09/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM04119

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Denied
1. No code information provided. Provide a thorough code analysis, that includes construction type, etc.

MECHANICAL REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Denied
E1.0 Needs combination emergency egress exit lights on each egress door. Needs rudimentary lighting for working in each
space.
Should have a minimum of 1 receptacle in each space, suggest one on each wall.

PLUMBING REVIEW COMMENTS:
Approved
06/09/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
06/30/2021 LOREN MAKUS ENGINEERING REVIEW Reqs Change A. This project is within a mapped flood hazard area and requires a Floodplain Use Permit (FUP.)
Please start a new FUP at our permit application web page: https://docs.tucsonaz.gov/Forms/tucsonpermitapp.
Instructions:
1. Is this for a new or existing activity application? - Please select New Application.

2. Submission Type - Select Floodplain Use Permit.

3. Project Name - Enter a name for your project.

4. Select Street Name from the list. You can type the first two letters or number to get closer to your choice in the list. Then select the rest of the address in the boxes provided.

5. Type of Permit - Select Commercial or Residential (Residential is for work on single family residences and duplexes.)

6. Complete the Applicant Info. (Note APA# is for applicants with an advance payment account. Leave blank is you do not have an APA account.

7. Complete the Contractor, Owner and Architect/Engineer sections as applicable.

8. Supporting Documentation Upload - Provide a complete cost estimate for the project. You may also provide additional documents you think will be helpful.

9. Sign the application and submit.

B. Show roof drainage patterns. Ensure sidewalks are kept flood free for up to a 10-year event.

C. A Development Package is required. See zoning comments.

Loren Makus, EIT
loren.makus@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
06/30/2021 VVERA1 OUT TO CUSTOMER Completed