Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T21CM04117
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/13/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
05/17/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
05/28/2021 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T21CM04117 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Approved ELECTRICAL REVIEW COMMENTS Approved MECHANICAL REVIEW COMMENTS: Denied 1. No mechanical equipment schedule provided for the new condensing units on the roof. Provide equipment schedule for new equipment. PLUMBING REVIEW COMMENTS: Denied 1. No waster and vent riser diagram provided. Provide a waste and vent riser diagram |
06/09/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
06/09/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
06/09/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/09/2021 | NGARCIA3 | OUT TO CUSTOMER | Completed |