Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM04114
Parcel: 10509546C

Address:
68 W RIVER RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM04114
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/13/2021 ROBERT SHERRY WATER REVIEW Completed
05/17/2021 JPEELDA1 FIRE REVIEW Approved
05/28/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM04114

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Approved

MECHANICAL REVIEW COMMENTS:
Denied
1. No mechanical equipment schedule provided for the new condensing units on the roof. Provide equipment schedule
for new equipment.

PLUMBING REVIEW COMMENTS:
Denied
1. No waster and vent riser diagram provided. Provide a waste and vent riser diagram
06/09/2021 STEVE SHIELDS ZONING REVIEW Approved
06/09/2021 SSHIELD1 ENGINEERING REVIEW Passed
06/09/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
06/09/2021 NGARCIA3 OUT TO CUSTOMER Completed