Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM04098
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/22/2021 | NMARTEL1 | ZONING | REVIEW | Approved | |
| 10/04/2021 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans. Update the code reference. Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits GENERAL COMMENTS: 1. Items built without permit may require alteration or improvement for achieving code compliance with the 2018 IRC, R105. This cannot be determined without an evaluation by a qualified professional. Complete construction plans are required for processing a building permit. The plans should show necessary structural changes for achieving building code compliance. FOUNDATION PLAN: 1. Dimension the footing length, width, and depth into undisturbed soil for each footing type and condition, R403.1.1. Show the width and length with rebar placement. FRAMING PLAN: 1. Provide a complete roof framing plan with beams and rafters sized with appropriate load carrying capacity, R301.1. The 2" x 7" @ 24" o.c. rafters are undersized for the 16‘ span. Consider 2" x 8" @ 16" o.c. or 2" x 10" @ 24" o.c. SECTIONS - DETAILS: 1. Show the Post Section Detail with #4 rebar in the appropriatly sized footing, R403.1. 2. Notate and specify the size and length of anchor bolts, R403.1. 3. Show the thickness of roof sheathing, R802.1. Please contact the plans reviewer if you have any questions: Ken Van Karsen 520 837-4912 City of Tucson Residential Plan Review |