Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T21CM03996
Parcel: 14041867A

Address:
3350 E WESTCO PL

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T21CM03996
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/27/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM03996

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide Structural Calculations for the Foundations and Roof Framing per Section 1601.1 of International Building Code 2018.
2. Provide Wind Load Calculations for the Bents per Section 1609 of International Building Code 2018.
3. Provide Seismic Calculations for the Bents per Section 1613 of International Building Code 2018.
4. All Calculations shall be sealed and signed by Professional Engineer registered with State of Arizona per Section 107.1 of International Building Code 2018.
5. Locate Sections shown on Drawing S2.1 on the Foundation Plan S2.2.
6. Provide Geotechnical Report for the proposed building per International Building Code 2018, Section 1803.1.
7. The Drawing S2.1 Design Criteria calls for 2015 Tennessee Building Code. Make revisions per latest codes for the
State of Arizona.
8. The Wind Pressures for components and cladding references ASCE7-10. Make revisions per IBC 2018.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/27/2021 NGARCIA3 OUT TO CUSTOMER Completed