Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM03996
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/06/2021 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T21CM03996 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Conditionally Approved 1. Show Geotechnical Report for the proposed building per International Building Code 2018, Section 1803.1 to the Inspector. The Inspector to verify info on Drawing S2.2 against the Geotechnical report. BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: Denied 1-Provide mechanical sheets describing the mechanical scope of work, exhaust and intake (for ventilation) technical information schedules, ventilation rate calculations, equipment location, equipment tag number identification and installation details. FMC-(A) 106.3.1 -Make sure to provide roof guards to comply with FMC-(BE)304.11 ELECTRICAL REVIEW COMMENTS Approved PLUMBING REVIEW COMMENTS: Denied 1-As per previous comment, provide minimum number of required plumbing fixtures calculations, as per IPC-Table-403.1 for Storage-1 occupancy classification. Show on plans, new or existing water closets, lavatories, utility sink and drinking fountain. |
| 07/14/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 07/16/2021 | JGARCIA1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed |