Review Date Reviewer's Name Type of Review Description Status Comments
05/17/2021 JPEELDA1 FIRE REVIEW Approved
05/26/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM03996

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
1. Show Geotechnical Report for the proposed building per International Building Code 2018,
Section 1803.1 to the Inspector. The Inspector to verify info on Drawing S2.2 against the
Geotechnical report.

BUILDING REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Denied
E-1.04: Need to provide single line diagram with short circuit fault calculation to panel. Need to provide for future loading docks as well. This is to confirm that the 10 KAIC rating of the panel is sufficient. If the feeder panel (panel PD1 power source) is below 10 KAIC state that you are feeding from such a panel and that is acceptable. Otherwise perform calculation from feeder panel.

MECHANICAL REVIEW COMMENTS:
Denied
1-Provide ventilation rate calculation and provisions to achieve natural or forced ventilation. FMC-403.3.1

PLUMBING REVIEW COMMENTS:
Denied
On the architectural sheets there is no mention of what is the occupancy classification or construction building type. Comply with IBC -Table 403.1.1
06/07/2021 STEVE SHIELDS ZONING REVIEW Reqs Change
06/07/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
06/17/2021 LOREN MAKUS ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/17/2021 VVERA1 OUT TO CUSTOMER Completed