Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T21CM03957
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/11/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Show the proposed exhaust fan installed per the manufacturer’s installation instructions (e.g. inlet and outlet ducts to be 3 times the equivalent duct diameter). Reference: Section 304.1, IMC 2018. |
| 05/14/2021 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 05/27/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/07/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. Provide complete electrical plans sealed by a Registrant registered in the State of Arizona. Show the wiring methods, branch circuit and panel designation for the new 3 phase exhaust fan and any other electrical equipment utilized in this project. Include a complete panel schedule including load calculations for the added load. Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/08/2021 | NGARCIA3 | OUT TO CUSTOMER | Completed |