Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM03798
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/19/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. The 2nd electrical plan submittal did not satisfy the requirements for total compliance of the Outdoor Lighting Code as specified in per section 104. Provide plans and evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code. Provide lighting plans with the following information on the plans; Size of the parcel in acres. See table 401.1, lighting area and option and indicate this information in the lighting site plan and or exterior lighting plan. 402.1 (light source color temperature requirements), shielding requirements, etc . Provide calcs for total lumens allowed and total lumens proposed per acre including existing, for Full Cut Off and Unshielded per table 401.1. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2. Specify any exceptions used. Curfew lighting controls If applicable. Do not confuse the Outdoor Lighting Code with the IECC. Ref; 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC), 2018 IBC sec 107.2.1. |