Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T21CM03798
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/13/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 05/17/2021 | ARUIZ1 | COMMUNICATIONS | REVIEW | Completed | |
| 05/17/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/01/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. It appears the new Cell Site is adjacent to Residential property. Please verify compliance with the 2012 Tucson/Pima County Outdoor Lighting Code. See section 104 for plan/permit submittal requirements. Also see section 401.3.1 through 401.3.3. Provide a complete description of the pole mounted luminaires as required in the Outdoor Lighting Code. Show wiring methods for the lighting installation on the power plan. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC), City of Tucson Commercial Plan Submittal Requirements |
| 06/09/2021 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 06/09/2021 | PETER MCLAUGHLIN | PLANNING-CITY HALL | REVIEW | Approved | |
| 06/15/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/15/2021 | VVERA1 | OUT TO CUSTOMER | Completed |