Permit Number: T21CM03784
Parcel: 126070650

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM03784
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/08/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM03784 R1

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

SECTIONS - DETAILS:

Show exterior wood siding, sheathing and wall framing with a 6” clearance above the ground (R317.1 item 5) with minimum ½” diameter anchor bolts, 7” embedment, R602.10.8 & R403.1.6. This may require a concrete stem when the floor is less than 6” above grade.

ELECTRICAL PLANS:

Show the location of the sub panel. Panelboards and overcurrent protection devices shall not be in clothes closets or bathrooms, E3405.5.

Show Bathroom receptacles on a separate 20 AMP circuit (dedicated) with outlets at no other rooms, E3703.4 and E3901.6.


If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
11/09/2021 NMARTEL1 ZONING REVIEW Approved