Permit Number: T21CM03739
Parcel: 11104156C

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T21CM03739
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/05/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The 2018 International Mechanical Code and the International Fuel Gas Code, both with Local Amendments are the relevant codes for this project
2. Show how the specified propane-fired unit heaters will be supported from the greenhouse structure. Reference: Section 920.2, IMC 2018.
3. Show how the specified propane-fired unit heaters will be vented and show the required clearances from combustible materials. Reference: Sections 501.15.4 and 503.2, IFGC 2018.
05/05/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The subject property is located within the jurisdiction of the City of Tucson, not Pima County. The City of Tucson has adopted the 2018 International building codes. The local amendments to the building codes can be found at https://www.tucsonaz.gov/pdsd/building-codes
2. Provide water demand and water pressure calculations (to include the pressure drop due to the reduced pressure backflow preventer) to verify that the existing 5/8” water meter and water service piping is adequate for the existing building and the proposed greenhouse use. Reference: Section 602.1, IPC 2018.
3. Show the size, route of the water supply piping and the shut-off valves that will serve the wet wall. Show how the piping will be protected from freezing. Reference: Sections 305.4, 603.1, and 606.2, IPC 2018.
4. Propane-fired space heaters are specified for the greenhouse; show the location and capacity of the propane storage tank as well as the propane distribution piping. Reference: Section 305.1, IFGC 2018.
05/05/2021 ROBERT SHERRY WATER REVIEW Reqs Change A reduced pressure zone backflow prevention assembly is required to protect the municipal water distribution system whenever pesticide, herbicide, fertilizer and chemical applicators are used on site (other than typical in-home use). http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf
05/13/2021 JPEELDA1 FIRE REVIEW Approved
05/25/2021 SAFEBUILT ELECTRICAL-COMMERCIAL REVIEW Passed
05/25/2021 SAFEBUILT BUILDING-COMMERCIAL REVIEW Reqs Change Activity Number: T21CM03739

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
NA

BUILDING REVIEW COMMENTS:
Denied
1. The listed applicable adopted codes are incorrect. Provide the correct adopted codes on the cover sheet.
2. Provide a thorough code analysis.

ELECTRICAL REVIEW COMMENTS
Approved

MECHANICAL REVIEW COMMENTS:
NA

PLUMBING REVIEW COMMENTS:
NA
06/03/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM03739
3402 E Kleindale Rd.
Green House Addtions

TRANSMITTAL: June 3, 2021
This site is located in the C-2zone (UDC 4.7.21).

1. Clarify what the existing use is on site as defined within the Unified Development Code.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
06/09/2021 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. Clarify the use of the property. If residential, provide a complete plot plan. If commercial, provide a separate development package.
07/15/2021 JGARCIA1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/15/2021 VVERA1 OUT TO CUSTOMER Completed