Permit Number: T21CM03688
Parcel: 109250220

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM03688
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/05/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
05/05/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise the mechanical design as required to avoid using the corridor as a return air duct (i.e. provide air returns for offices 1 and 2). Reference: Section 601.2, IMC 2018.
05/05/2021 ROBERT SHERRY WATER REVIEW Completed
05/13/2021 JVINCEN1 FIRE REVIEW Approved
05/19/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet C1; Code Review Checklist (Allowable Area): This checklist indicates 27,000 SF allowed per the IBC Table 506.2. That table indicates an allowable SF of 9000 for a non-sprinklered B Occupancy Classification. Please revise.
2. Sheet C1; Code Review Checklist (Allowable Stories/Building Height): This checklist indicates 3 Story/60' Height allowed per the IBC Tables 504.3 and 504.4. Those tables indicate 2 Story/40' for a non-sprinklered B Occupancy Classification. Please revise.
3. Sheet C1; Code Review Checklist (Travel Distance to Exit): This checklist indicates a 200' maximum travel distance allowed per the IBC Table 1017.2. Since this space has only one exit, the IBC Table 1006.2.1 must be used to determine the maximum travel distance (100'). Please revise.
4. Sheet C1; Code Review Checklist (Dead End Corridor): This checklist indicates the IBC Section 1018.4 for the dead end corridor requirements. Please revise.
5. Sheet C1; Code Review Checklist (Dead End Corridor): This checklist indicates a maximum dead end corridor length of 50'. Per the IBC Section 1020.4, the maximum length of the dead end corridor is 20' (50' if sprinklered). Please revise.
6. General: Please provide a written response to all review comments.
05/25/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

1. The panel schedule shows the panel as 6- Existing and the line diagram shows ‘Panel C’ as new..Please clarify.

2. Show the location of the Electrical Service, Panel, AC Unit, Water Heater, and associated disconnecting means on the power plan and identify correctly.

3. Show the location of the Mecnical Equipment and Receptacle on the roof.

4. The currently adopted IECC is the 2018 and the allowable wattage per sq.ft for the office lighting is .79 watts per sqft.. IECC Table C405.3.2(1).

5. Designate branch circuits and panel for all new receptacles and bathroom exhaust fan.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements.
06/02/2021 SSHIELD1 ENGINEERING REVIEW Passed
06/02/2021 STEVE SHIELDS ZONING REVIEW Approved
06/02/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed