Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T21CM03685
Parcel: 13816001G

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM03685
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/04/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Show how each hand sink and floor sink will be vented in accordance with one of the methods shown in the IPC. Reference: Section 901.2.1, IPC 2018.
05/04/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Spaces in which factory-built recirculating hoods (i.e. ventless hoods) tested in accordance with UL 710B are installed are considered to be kitchens and shall be ventilated per Section 403.3.1.1, IMC 2018. The minimum exhaust rate for the space shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.1, exception 2, IMC 2018.
05/04/2021 ROBERT SHERRY WATER REVIEW Completed
05/13/2021 JVINCEN1 FIRE REVIEW Approved
05/19/2021 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/19/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/26/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/03/2021 SSHIELD1 ENGINEERING REVIEW Passed
06/03/2021 STEVE SHIELDS ZONING REVIEW Approved