Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T21CM03620
Parcel: 12111162C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM03620
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/10/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed, no new drawings. [Initial comment: Verify that the new conference room has adequate ventilation. Reference: Section 403.3.1.1, IMC 2018.]
2. Comment not addressed, no new drawings. [Initial comment: The new reflected ceiling plan shows only two returns for the combined suites, presumably serving two rooftop AC units. Revise the mechanical design as required to avoid using the corridors as return air ducts. Reference: Section 601.2, IMC 2018.
06/21/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved