Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM03620
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/10/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Comment not addressed, no new drawings. [Initial comment: Verify that the new conference room has adequate ventilation. Reference: Section 403.3.1.1, IMC 2018.] 2. Comment not addressed, no new drawings. [Initial comment: The new reflected ceiling plan shows only two returns for the combined suites, presumably serving two rooftop AC units. Revise the mechanical design as required to avoid using the corridors as return air ducts. Reference: Section 601.2, IMC 2018. |
| 06/21/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |