| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/03/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 05/03/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Verify that the new conference room has adequate ventilation. Reference: Section 403.3.1.1, IMC 2018. 2. The new reflected ceiling plan shows only two returns for the combined suites, presumably serving two rooftop AC units. Revise the mechanical design as required to avoid using the corridors as return air ducts. Reference: Section 601.2, IMC 2018. |
| 05/03/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 05/10/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 05/13/2021 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 05/18/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A4.0; Section 6: Per the IBC Section 1109.3, the sink must be accessible. Per the 2009 ICC/ANSI Section 606.3, the height of the sink must be a maximum of 34". Please revise the Section and Elevation 2. |
| 05/25/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/03/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 06/03/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |