Permit Number: T21CM03620
Parcel: 12111162C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM03620
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/03/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
05/03/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Verify that the new conference room has adequate ventilation. Reference: Section 403.3.1.1, IMC 2018.
2. The new reflected ceiling plan shows only two returns for the combined suites, presumably serving two rooftop AC units. Revise the mechanical design as required to avoid using the corridors as return air ducts. Reference: Section 601.2, IMC 2018.
05/03/2021 ROBERT SHERRY WATER REVIEW Completed
05/10/2021 SBLOOD1 ENGINEERING REVIEW Passed
05/13/2021 JVINCEN1 FIRE REVIEW Approved
05/18/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A4.0; Section 6: Per the IBC Section 1109.3, the sink must be accessible. Per the 2009 ICC/ANSI Section 606.3, the height of the sink must be a maximum of 34". Please revise the Section and Elevation 2.
05/25/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/03/2021 STEVE SHIELDS ZONING REVIEW Approved
06/03/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed