Permit Number: T21CM03545
Parcel: 14022001A

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T21CM03545
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/29/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
04/29/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide an approved vacuum relief valve for the scheduled bottom-fed water heater that is located above the fixture outlets. Reference: Section 504.2, IPC 2018.
2. Provide a watertight pan of galvanized steel, aluminum, or other approved material under the water heater with a drain to an approved location. Reference: Section 504.7, IPC 2018.
04/29/2021 ROBERT SHERRY WATER REVIEW Completed
05/13/2021 JPEELDA1 FIRE REVIEW Approved
05/13/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/24/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/01/2021 STEVE SHIELDS ZONING REVIEW Reqs Change UNTIL DP21-0109 HAS BEEN FULLY APPROVED ZONING CANNOT APPROVE THIS BUILDING PLANS
06/07/2021 LOREN MAKUS ENGINEERING REVIEW Approved
07/07/2021 DBENOIT1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Reqs Change

Final Status

Task End Date Reviewer's Name Type of Review Description
07/07/2021 DBENOIT1 APPROVAL SHELF Completed
07/07/2021 DBENOIT1 OUT TO CUSTOMER Completed
07/07/2021 DBENOIT1 REJECT SHELF Completed