Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T21CM03540
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/28/2021 | PCAMARE1 | ENGINEERING | REVIEW | Passed | |
| 05/10/2021 | AWARNER1 | NPPO | REVIEW | Passed | |
| 05/17/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM03540 4768 S Camino Paso Doble Storage Room Addition TRANSMITTAL: May 17, 2021 COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1). This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10. 1. The minimum setback to a side street property line is ten (10) feet (UDC Section 6.4.5.C.1.b). As the plans were not readable the proposed side street perimeter yard setback and not be verified but as it is less than 10’-0” a Design Development Option (DDO) will need to be submitted and approved. DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. A DDO is a separate submittal from the building plan and shall be submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type “Zoning Administration”. If you have questions about the DDO application or process please contact Mark Castro at Mark.Castro@tucsonaz.gov. Additional comments that will need to be addressed: 2. The submitted plans are not readable please have them scanned and ensure that they are readable prior to submitting. 3. Permit #T19CM02720 will need to finialed prior to final inspection of this permit. |
| 05/24/2021 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | Provide plans with legible lettering. Show the minimum 12" footing depth below the undisturbed ground surface (R403.1) with 12" minimum width for wood framed walls R403.1.1. Show exterior wood siding, sheathing and wall framing with a 6" clearance above the ground (R317.1 item 5) with minimum ½" diameter X 7" embedment anchor bolt and treated sill plates, R602.10.8 & R403.1.6. |