Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T21CM03537
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/28/2021 | LBOWERS1 | BUILDING-RESIDENTIAL | REVIEW | Needs Review | |
| 05/10/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 06/01/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM03537 65 E Calle Claravista Master bedroom Addition TRANSMITTAL: June 1, 2021 COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1). This site is located in the RX-2 zone (UDC 4.7.7). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-1). See Use-Specific Standards 4.9.7.6. The minimum setback is twenty feet facing each interior property line (Table 6.3-1.A). Proposed perimeter yard setback from the proposed addition to the east property line is 14’-2”. DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. A DDO is a separate submittal from the building plan and shall be submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type “Zoning Administration”. If you have questions about the DDO application or process please contact Mark Castro at Mark.Castro@tucsonaz.gov. |
| 06/01/2021 | SSHIELD1 | NPPO | REVIEW | Passed |