Permit Number: T21CM03532
Parcel: 115046760

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM03532
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/29/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide ready access to the washer box. Reference: Section 802.4, IPC 2018.
2. Clarify the existing waste and vent piping. It appears that the new fixture drain from the stacked washer/dryer is connecting to the vent for the existing water closet. Reference: Section 911.1, IPC 2018.
04/29/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Clarify the location of the dryer exhaust termination with regard to the building openings. Reference: Section 501.3.1 (2), IMC 2018.
04/29/2021 ROBERT SHERRY WATER REVIEW Completed
05/05/2021 SBLOOD1 ENGINEERING REVIEW Passed
05/13/2021 JPEELDA1 FIRE REVIEW Approved
05/17/2021 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/17/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/25/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/03/2021 STEVE SHIELDS ZONING REVIEW Approved