Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM03532
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/29/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide ready access to the washer box. Reference: Section 802.4, IPC 2018. 2. Clarify the existing waste and vent piping. It appears that the new fixture drain from the stacked washer/dryer is connecting to the vent for the existing water closet. Reference: Section 911.1, IPC 2018. |
| 04/29/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Clarify the location of the dryer exhaust termination with regard to the building openings. Reference: Section 501.3.1 (2), IMC 2018. |
| 04/29/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 05/05/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 05/13/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 05/17/2021 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 05/17/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/25/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/03/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved |