Permit Number: T21CM03511
Parcel: 13402003F

Address:
707 S GOLLOB RD

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM03511
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/15/2021 STEVE SHIELDS ZONING REVIEW Approved
06/23/2021 AWARNER1 NPPO REVIEW Approved
06/29/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM03511 R1
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL COMMENTS:

1. All construction drawings submitted after June 1, 2010 for one- or two-family dwellings must provide gray water utilization or preparation, Ordinance #10579/11089 revised July 9, 2013. Provide a complete code compliant working gray water system or a preparation as illustrated with the details at https://www.tucsonaz.gov/files/pdsd/codes-ordinances/Grey_Water_Options_FINAL_.pdf
When the clothes washer is not near an exterior wall show a gray water bathing fixture drain looped 3’ beyond an exterior wall below grade before connection to the building drain. This provides a future connection point for collection and code compliant discharge.

PLUMBING PLANS:

1. When specifying a gray drain line include a listed diverter valve and complete collection and discharge system consistent with P3009 for Recycling Systems with backflow and overflow provision. The system design must provide a means of discharge to the building drain system when the gray water system is not operational, Arizona Department of Environmental Quality publication #C07-01.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
07/08/2021 JPEELDA1 FIRE REVIEW Approved