Permit Number: T21CM03508
Parcel: 13316033F

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM03508
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/10/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A000; Drawing Index: Please revise the Drawing Index to include all sheets in this submittal.
2. Sheet A000; Special Inspections: Please indicate all special inspections required for this project, and provide a Special Inspections Certificate with Parts A and B completed. This form may be found at www.tucsonaz.gov/PDSD.
3. Sheet S1.1; Detail A1: Where is this detail located? Is this an existing wall? Please verify.
4. General: Please provide structural calculations for the new Flexmod unit structure, the foundation (slab), and the connection of the unit to the foundation. All Flexmod calculations and drawings must be sealed, signed, and dated by a registered design engineer.
5. General: Please provide written responses to all review comments.
08/12/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
08/24/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM03508
6464 E Tanque Verde Rd – C-2
Site Fence & Accessory Structures (Flexmode)

TRANSMITTAL: August 24, 2021
This site is located in the C-2 zone (UDC 4.7.21). Marijuana Dispensary is a permitted use subject to Use Specific Standard 4.9.9.E.1.

1. This comment was not addressed. As site work is proposed, fencing and flexmode additions a Development Package (DP) meeting the requirements of Administrative Manual (AM) 2-06 shall be submitted and approved prior to approval of this plan. The DP is a separate submittal from the building plan and is submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using the submission type Site Review”.

2. As you are proposing an expansion of use area for a Marijuana Dispensary a new Marijuana Location approval letter must be applied for, requirements can be found at https://www.tucsonaz.gov/files/pdsd/forms/medical_marijuana_application_031512.pdf.

3. Per UDC Article 4.9.9.E.1.b A medical marijuana dispensary shall be located in a permanent building and shall not be located in a trailer, cargo container, mobile or modular unit, mobile home, recreational vehicle, or other motor vehicle. The proposed Flexmod does not meet this requirement.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
08/24/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved