Permit Number: T21CM03504
Parcel: 133300490

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T21CM03504
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/10/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM03504
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL COMMENTS:

1. Items built without permit or accurate information require alteration or improvement for achieving code compliance with the 2018 IRC, R105.

FLOOR PLANS:

1. Exterior walls with a fire separation distance less than 3-foot to the property line require not less than one-hour fire-resistive construction. Show compliance with R302.1 (City of Tucson Amended) by providing a section detail of materials prescribed in IBC Table 721.1(2), Items 15-1.1 to 16-1.3.
2. Roof projections may not extend to a point closer than 2 feet from the property line. Show compliance with R302.1 (City of Tucson Amended) by removing the roof overhang close to the property line.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/02/2021 DBENOIT1 APPROVAL SHELF Completed
09/02/2021 DBENOIT1 OUT TO CUSTOMER Completed
09/02/2021 DBENOIT1 REJECT SHELF Completed