07/25/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM03490 REV1

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Denied
1. Provide the hood sizing calculations along with the equipment that will be present.


MECHANICAL REVIEW COMMENTS:
Denied
Provide complete mechanical plans along with application and scope of work (IMC2018,106.3.1)


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
Prior submittal was approved. This seems to be equipment submittals (probably with minor revisions) and is approved for the project.


PLUMBING REVIEW COMMENTS:
Denied
1). Include approved plans for reference to see if any of the revisions affected the original approved gas plans. -IFGC 106.3.1