Permit Number: T21CM03490
Parcel: 132191450

Address:
2150 E AJO WY

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T21CM03490
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/03/2021 ROBERT SHERRY WATER REVIEW Reqs Change Reduced pressure backflow prevention assemblies are required to be installed directly after the water meter for buildings that have food service facilities and in locations accessible to Tucson Water. (See the development package, DP21-0029, for the actual location of the water meter and the reduced pressure backflow preventer.) Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf.
05/11/2021 JPEELDA1 FIRE REVIEW Approved
05/25/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM03490

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide Structural Calculations for Foundations, Columns, Roof Framing for the canopies per Section 1601.1 of
International Building Code 2018.
2. Provide Wind Load Calculations for the canopies per Section 1609 of International Building Code 2018.
3. Provide Seismic Calculations for the canopies per Section 1613 of International Building Code 2018.
4. All Calculations shall be sealed and signed by Professional Engineer registered with State of Arizona per Section 107.1 of
International Building Code 2018.
5. Provide Geotechnical Report for the proposed building per International Building Code 2018, Section 1803.1.
6. Structural steel, components and fasteners for the roof screen are to be protected against corrosion in accordance with
AISC 360 Section B.13 as indicated in IBC 2018 Section 2203.1.
7. Designer is to coordinate venting and drainage hole requirements for HSS tube members that are galvanized using the
hot-dip galvanizing process. Provide for plugs as needed.
AWS D-19.0 calls for welds on galvanized steel to be free of zinc. Field welds on galvanized parts requires the removal of the
zinc coating in the area of weld. Provide zinc paint (approved by the galvanizer) and apply as required to the weld and steel
area to provide protection.
8. Roof drainage and secondary drains are to comply with IBC 1502.1.
9. The Structural Calculations submitted calls for Occupancy Group B. The Drawing Project Cover Sheet (PCS) calls for
Construction Type A-2. Make amendments as needed.
10. Provide Foundation Info on Drawing S1.1 for the Canopies. No foundation info has been provided.
11. Refer to Drawing S2.1 Patio/Trellis Framing Plan. Column at D and 3 is missing. Revise Drawing.
12. Refer Drawing S1.1, Canopy Foundation Plan It shows Sections 1/S1.3 thru 11/S1.3. Drawing S1.3 is not submitted in
this package. Nor it is present in Index of Drawings on the cover sheet PCS. Provide/Revise Drawing.
13. Submit a response letter addressing these correction items and provide bubbles on the revisions to the drawings.

BUILDING REVIEW COMMENTS:
Denied
1. Sheet CRA is missing out of the submitted set. Please resubmit this sheet.
2. No structural review completed

ELECTRICAL REVIEW COMMENTS
Denied
E2.1B: Comments:
30 amp disconnects called out when Circuit amps are 36 and 42 amps on MAU condensers 1 & 2.
Conductors for RTU-1 and RTU-2 should be sized for CB provided and called out

MECHANICAL REVIEW COMMENTS:
Denied
The City of Tucson has adopted the 2018 International Building Codes with local amendments. The codes are updated every
three years to reflect the latest standards of life-safety and developments in building science. Effective January 1st, 2019 all
new applied permit activity will use the 2018 Codes. Please update note(s) on page M3. 2 #5. Demonstrate compliance.

PLUMBING REVIEW COMMENTS:
Denied
The City of Tucson has adopted the 2018 International Building Codes with local amendments. The codes are updated every
three years to reflect the latest standards of life-safety and developments in building science. Effective January 1st, 2019 all
new applied permit activity will use the 2018 Codes. Please update note(s) on page P5.1 #2. Demonstrate compliance.
05/26/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM03490
2150 E Ajo Way
New Raising Canes Restaurant

TRANSMITTAL: May 26, 2021
This site is located in the C-2 zone (UDC 4.7.21). Food service is a permitted use (Table 4.8-4) subject to Use Specific Standards 4.9.4.M.1 and 4.9.13.P.

1. Zoning has reviewed the proposed building for compliance with DP21-0029 and although it appears to match the DP unit DP21-0029 is approved Zoning cannot approve the building plan.

2. As it appears that you will be providing the DP sheets in the building set the DP sheets will either need to be the stamped approved sheets, or marked as for reference only.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
05/26/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
05/28/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change Engineering has reviewed the building plans for compliance with DP21-0029 and although the building plans appear to match the DP until the DP is approved Engineering cannot approve the building plans.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
05/28/2021 NGARCIA3 OUT TO CUSTOMER Completed