Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T21CM03490
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/03/2021 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Reduced pressure backflow prevention assemblies are required to be installed directly after the water meter for buildings that have food service facilities and in locations accessible to Tucson Water. (See the development package, DP21-0029, for the actual location of the water meter and the reduced pressure backflow preventer.) Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf. |
| 05/11/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 05/25/2021 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T21CM03490 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Denied 1. Provide Structural Calculations for Foundations, Columns, Roof Framing for the canopies per Section 1601.1 of International Building Code 2018. 2. Provide Wind Load Calculations for the canopies per Section 1609 of International Building Code 2018. 3. Provide Seismic Calculations for the canopies per Section 1613 of International Building Code 2018. 4. All Calculations shall be sealed and signed by Professional Engineer registered with State of Arizona per Section 107.1 of International Building Code 2018. 5. Provide Geotechnical Report for the proposed building per International Building Code 2018, Section 1803.1. 6. Structural steel, components and fasteners for the roof screen are to be protected against corrosion in accordance with AISC 360 Section B.13 as indicated in IBC 2018 Section 2203.1. 7. Designer is to coordinate venting and drainage hole requirements for HSS tube members that are galvanized using the hot-dip galvanizing process. Provide for plugs as needed. AWS D-19.0 calls for welds on galvanized steel to be free of zinc. Field welds on galvanized parts requires the removal of the zinc coating in the area of weld. Provide zinc paint (approved by the galvanizer) and apply as required to the weld and steel area to provide protection. 8. Roof drainage and secondary drains are to comply with IBC 1502.1. 9. The Structural Calculations submitted calls for Occupancy Group B. The Drawing Project Cover Sheet (PCS) calls for Construction Type A-2. Make amendments as needed. 10. Provide Foundation Info on Drawing S1.1 for the Canopies. No foundation info has been provided. 11. Refer to Drawing S2.1 Patio/Trellis Framing Plan. Column at D and 3 is missing. Revise Drawing. 12. Refer Drawing S1.1, Canopy Foundation Plan It shows Sections 1/S1.3 thru 11/S1.3. Drawing S1.3 is not submitted in this package. Nor it is present in Index of Drawings on the cover sheet PCS. Provide/Revise Drawing. 13. Submit a response letter addressing these correction items and provide bubbles on the revisions to the drawings. BUILDING REVIEW COMMENTS: Denied 1. Sheet CRA is missing out of the submitted set. Please resubmit this sheet. 2. No structural review completed ELECTRICAL REVIEW COMMENTS Denied E2.1B: Comments: 30 amp disconnects called out when Circuit amps are 36 and 42 amps on MAU condensers 1 & 2. Conductors for RTU-1 and RTU-2 should be sized for CB provided and called out MECHANICAL REVIEW COMMENTS: Denied The City of Tucson has adopted the 2018 International Building Codes with local amendments. The codes are updated every three years to reflect the latest standards of life-safety and developments in building science. Effective January 1st, 2019 all new applied permit activity will use the 2018 Codes. Please update note(s) on page M3. 2 #5. Demonstrate compliance. PLUMBING REVIEW COMMENTS: Denied The City of Tucson has adopted the 2018 International Building Codes with local amendments. The codes are updated every three years to reflect the latest standards of life-safety and developments in building science. Effective January 1st, 2019 all new applied permit activity will use the 2018 Codes. Please update note(s) on page P5.1 #2. Demonstrate compliance. |
| 05/26/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM03490 2150 E Ajo Way New Raising Canes Restaurant TRANSMITTAL: May 26, 2021 This site is located in the C-2 zone (UDC 4.7.21). Food service is a permitted use (Table 4.8-4) subject to Use Specific Standards 4.9.4.M.1 and 4.9.13.P. 1. Zoning has reviewed the proposed building for compliance with DP21-0029 and although it appears to match the DP unit DP21-0029 is approved Zoning cannot approve the building plan. 2. As it appears that you will be providing the DP sheets in the building set the DP sheets will either need to be the stamped approved sheets, or marked as for reference only. If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov. |
| 05/26/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 05/28/2021 | SBLOOD1 | ENGINEERING | REVIEW | Reqs Change | Engineering has reviewed the building plans for compliance with DP21-0029 and although the building plans appear to match the DP until the DP is approved Engineering cannot approve the building plans. Stephen Blood (520) 837-4958 Stephen.blood@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/28/2021 | NGARCIA3 | OUT TO CUSTOMER | Completed |