Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM03480
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/11/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Passed
05/20/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change This installation falls under a hazardeous location per NEC art 514 and 515. Please provide plans sealed by an electrical Engineer registered in the State of Arizona..
Ref; 2018 IBC, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.Electrical Requirements:
• Electrical Plans
Fully dimensioned floor plan showing location and assigned circuit numbers of all outlets,
luminaires, switches, appliances, panels, motors, disconnects, electrical and HVAC equipment.
All home runs should indicate panel name or number. A Registered Electrical Engineer is
required when electrical designs exceed 400 amps, and where the available fault current at any
new piece of equipment exceeds 22,000 amps, or for hazardous locations, hospitals or buildings
with operating rooms.
05/28/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM03480
7601 E Tanque Verde Rd
New Propane Tank

TRANSMITTAL: May 28, 2021
This site is located in the C-1 zone (UDC 4.7.20).

1. As a new structure, propane tank, is being added to a commercial site a Development Package (DP), commercial site plan, is required. This DP shall meet the requirements of the checklist for Minor Changes to Commercial/Industrial Sites found at: https://www.tucsonaz.gov/files/pdsd/forms/Minor_Changes_to_Commercial_Industrial_Sites_.pdf. This DP is a separate submittal from the building permit and shall be submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using the “Submission Type”, “Site Review”

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.