Permit Number: T21CM03397
Parcel: 30503005C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM03397
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/06/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Approved CONDITIONALLY APPROVED PENDING FIRE APPROVAL
07/15/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T21CM03397
10505 S Wilmot Rd
TPD Evidentiary Vehicle Storage Building (2nd Review)

TRANSMITTAL DATE: July 15, 2021

This site is located in the RH zone (UDC 4.7.8). Protective Service (government owned and operated only) is a permitted use in this zone (Table 4.8-2)

1. The building plans have been reviewed for compliance with DP21-0065 and although it appears that the building plans match the DP until the DP is approved Zoning cannot approve the building plans.

If you have any questions about this transmittal, please contact Elisa Hamblin or Elisa.Hamblin@tucsonaz.gov.
07/16/2021 JGARCIA1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
07/19/2021 SBLOOD1 ENGINEERING REVIEW Approved
08/03/2021 JPEELDA1 FIRE REVIEW Reqs Change Fire hydrant shall either be added and or relocated from back storage yard to front rounded curb entry area and or a new one added in this area. Recommend adding a new one to give fire some assistance if there was a fire in the storage yard.
FDC shall be located on the street side of the building not behind a protected fence. KNOX caps required for the FDC.

Questions:
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033