Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T21CM03395
Parcel: 13727635B

Address:
1855 W DREXEL RD

Review Status: Completed

Review Details: REVISION - - 3RD

Permit Number - T21CM03395
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM03395 REV3

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. All Drawings shall be sealed and signed by a Registered Architect or Professional Engineer Registered with State of Arizona per Section 107.1 of International Building Code 2018. The Drawings MF-1, SMF2, SMF3 AND SMF4 are not certified with seal and signatures.


BUILDING REVIEW COMMENTS:
N/A


MECHANICAL REVIEW COMMENTS:
N/A


ELECTRICAL REVIEW COMMENTS
N/A


PLUMBING REVIEW COMMENTS:
N/A


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
04/15/2022 NGARCIA3 OUT TO CUSTOMER Completed