Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T21CM03395
Parcel: 13727635B

Address:
1855 W DREXEL RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM03395
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/30/2021 SBLOOD1 ENGINEERING REVIEW Approved
05/03/2021 ROBERT SHERRY WATER REVIEW Completed
05/18/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Reqs Change
05/18/2021 JPEELDA1 FIRE REVIEW Approved
05/18/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T21CM03395
1855 W Drexel Rd
Addition and remodel to existing Fire Station (1st Review)

TRANSMITTAL DATE: May 18, 2021

This site is located in the R-2 zone (UDC 4.7.9). Protective Service (government owned and operated only) is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standard 4.9.13.F.

1. The building plans have been reviewed for compliance with DP20-0236 and although it appears that the building plans match the DP until the DP is approved Zoning cannot approve the building plans.

If you have any questions about this transmittal, please contact Elisa Hamblin or Elisa.Hamblin@tucsonaz.gov.
06/10/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM03395

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Denied
1. Details 20 and 21 shown on Drawing S1.5 are not marked anywhere on the Floor Plans. Remove these if they are not
used.
2. Roof drainage and secondary drains are to comply with IBC 1502.1.
3. Refer Drg. S1.0. Loads: Ultimate wind speed is correctly called as 115 mph. Design wind speed (Vasd) is
called 85 mph. Verify and make corrections as needed.

BUILDING REVIEW COMMENTS:
Denied
The R-3 fire area is required to be protected by an automatic sprinkler system per 903.2.8.1
2. The separation after the installation of the sprinkler system is required to be of 1 hour fire resistance rated construction
per Table 508.4. The separation is required to be fire barriers. Section 420 does not apply to mixed occupancies. The
R-3 requirements of Chapter 9 apply as they are the most restrictive per Section 508.4.1.

MECHANICAL REVIEW COMMENTS:
Denied
Update equipment ID numbering sequence(s) on Mechanical Details Sheets M2.0 and M2.1

ELECTRICAL REVIEW COMMENTS
Denied
E0.2 ELECTRICAL SITE PLAN: Confirm #10 AWG grounding to ground rod is acceptable for pole base.
E1.0 LIGHTING PLAN: Confirm or correct Note #2 for bottom of lights to be 16 inches AFF.
E4.0 ONE LINE DIAGRAM, PANEL SCHEDULES AND CALCULATION:
Where is panel BS as called out by Switchboard? Need to provide conduit/conductor information and
arc flash calculation too.
New Switchboard has circuit breakers for panels B, M, and A. Are the Fused disconnects still in the
design as shown? If so, call out in note or redraw as design implies three sets of conductors sharing
one conduit to a shared trough.

PLUMBING REVIEW COMMENTS:
Approved