Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM03394
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/29/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 04/30/2021 | SBLOOD1 | ENGINEERING | REVIEW | Approved | |
| 05/17/2021 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T21CM03394 GENERAL: o Provide written responses to all review comments. o Provide a complete plan set. o Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Denied 1. Geotechnical Report for the proposed building per International Building Code 2018, Section 1803.1 is not provided. Inspector to verify Foundation info on Drawing S1.0 and the Geotechnical Report. 2. Roof drainage and secondary drains are to comply with IBC 1502.1. 3. Refer Drg. S1.0. Loads: Ultimate wind speed is correctly called as 115 mph. Design wind speed (Vasd) is called 85 mph. Verify and make corrections as needed. BUILDING REVIEW COMMENTS: Denied 1. Provide an existing floor plan 2. Provide a demolition plan as applicable. No structural review completed. ELECTRICAL REVIEW COMMENTS Approved MECHANICAL REVIEW COMMENTS: Conditionally Approved NOTE: Every effort has been made to identify code violations. Any oversight by the reviewer shall not be considered as authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The designer is responsible for following all applicable federal, state, and municipal codes and ordinances. PLUMBING REVIEW COMMENTS: Conditionally Approved |
| 05/18/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM03394 7575 E Speedway Blvd Addition and remodel to existing Fire Station (1st Review) TRANSMITTAL DATE: May 18, 2021 This site is located in the RX-1 zone (UDC 4.7.6). Protective Service (government owned and operated only) is a permitted use in this zone (Table 4.8-1) subject to Use Specific Standard 4.9.13.F. 1. The building plans have been reviewed for compliance with DP20-0236 and although it appears that the building plans match the DP until the DP is approved Zoning cannot approve the building plans. If you have any questions about this transmittal, please contact Elisa Hamblin or Elisa.Hamblin@tucsonaz.gov. |
| 05/18/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 05/18/2021 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Code Summary Under Fire Protection: remove the fire sprinkler notes if not fire sprinklering Jennifer.Peel-Davis@Tucsonaz.gov 520-837-7033 |