Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T21CM03393
Parcel: 11807002J

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM03393
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2021 JPEELDA1 FIRE REVIEW Approved
07/13/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM03393

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Approved

MECHANICAL REVIEW COMMENTS:
Denied
1. Section 606.2.1 Return air systems. REVISE Section by DELETING sentence, but not Exception, and REPLACING it with the following: Duct smoke detectors shall be installed in the return duct of air distribution systems moving more than 2,000 cfm. Duct smoke detectors shall be located upstream of air filters or outside air inlets. Exception: Smoke detectors are not required in the return air system where all portions of the building served by the air distribution system are protected by area smoke detectors connected to a fire alarm system in accordance with the International Fire Code. Demonstrate compliance.
2. (E) AC-2: Equipment information is missing. Update plans

PLUMBING REVIEW COMMENTS:
Approved
07/21/2021 STEVE SHIELDS ZONING REVIEW Approved