Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM03391
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/28/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Show how each hand sink and floor sink will be vented in accordance with one of the methods shown in the IPC. Reference: Section 901.2.1, IPC 2018. |
| 04/28/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Spaces in which factory-built recirculating hoods (i.e. ventless hoods) tested in accordance with UL 710B are installed are considered to be kitchens and shall be ventilated per Section 403.3.1.1, IMC 2018. The minimum exhaust rate for the space shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.1, exception 2, IMC 2018. |
| 04/28/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 04/28/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 04/30/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 05/10/2021 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 05/10/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/19/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 05/24/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved |