Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM03386
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/28/2021 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Provide the size of the water meter serving this suite, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018. |
04/30/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
05/10/2021 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T21CM03386 GENERAL: o Provide written responses to all review comments. o Provide a complete plan set. o Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: NA BUILDING REVIEW COMMENTS: Denied 1. The cover indicates that this project is a level II alteration, however, the existing building code is not listed on the cover page under adopted building codes. Additionally, one must choose a compliance path. Choose to construct the space under the IEBC or the provisions of the IBC. Please indicate and clarify which compliance path is being taken. ELECTRICAL REVIEW COMMENTS Approved MECHANICAL REVIEW COMMENTS: Approved PLUMBING REVIEW COMMENTS: Approved |
05/11/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
05/24/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
05/24/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved |