Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM03382
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/01/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Comment not resolved. The building air balance schedule, the mechanical ceiling plan, the kitchen hood schedule, and the exhaust fan schedule are not coordinated. [Initial comment: Coordinate the building air balance schedule with the ventilation calculations and the HVAC design (e.g. no FC-5 is shown on the mechanical plans; FC-1 and FC-2 require 300 CFM of outside air). Reference: Section 107.2.1, IBC 2018.] 2. Verify that the new, proposed slot diffusers for the make-up air (for KH-1, keynote 5) will not disrupt the capture performance of the new exhaust hood. |
| 06/08/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |