Permit Number: T21CM03382
Parcel: Unknown

Address:
3894 N ORACLE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM03382
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Comment not resolved. The building air balance schedule, the mechanical ceiling plan, the kitchen hood schedule, and the exhaust fan schedule are not coordinated. [Initial comment: Coordinate the building air balance schedule with the ventilation calculations and the HVAC design (e.g. no FC-5 is shown on the mechanical plans; FC-1 and FC-2 require 300 CFM of outside air). Reference: Section 107.2.1, IBC 2018.]
2. Verify that the new, proposed slot diffusers for the make-up air (for KH-1, keynote 5) will not disrupt the capture performance of the new exhaust hood.
06/08/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved