Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM03309
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/04/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
05/12/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. Provide more detail for the canopy lighting wiring methods including the local disconnecting means required per NEC 225.31,32. Provide compliance with the 2012 Tucson Outdoor Lighting Code for the exterior canopy lighting. Ref; Plan Sheet PV2.1, PV2.3, and Lighting Site Plan. The line diagrams do not reflect the canopy lighting branch circuit. Provide a grounding detail for the 60KVA transformer Grounding Electrode . NEC 250.30. Verify that the PV DG Disconnect is rated as Suitable for use as Service Equipment. NEC 690.13(C). Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements |
05/20/2021 | SBLOOD1 | ENGINEERING | REVIEW | Reqs Change | Engineering has reviewed the building plans for compliance with DP21-0104 and although the building plans appear to match the DP until the DP is approved Engineering cannot approve the building plans. Stephen Blood (520) 837-4958 Stephen.blood@tucsonaz.gov |
06/30/2021 | SAMUEL ROGERS | ZONING | REVIEW | Approved |