Permit Number: T21CM03256
Parcel: 133165780

Address:
6500 E GRANT RD

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM03256
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/13/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

For clarity please indicate on the site plan which luminaires are new and existing, or existing being replaced.

Indicate with a note whether or not a special inspection is required per section 104.2.2 and 106.2. (OLC).

Provide compliance with the 2018 IECC for the exterior lighting. Do not confuse the Outdoor Lighting Code with the IECC

Provide for house Side Shielding if applicable per section 401.3

Ref; 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC), 2018 IBC sec 107.2.1. 2018 IECC.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/14/2021 IMONSHI1 OUT TO CUSTOMER Completed