Review Date Reviewer's Name Type of Review Description Status Comments
05/04/2021 NMARTEL1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL
Nicholas Martell, Planner
T21CM03254
New SFR
April 29, 2021
The residential plans have been reviewed by the Zoning Review Section but cannot be approved until all zoning comments or concerns have been addressed.
1. Zoning cannot approve until the grading development package is completed.
2. After the development package is completed, please resubmit the plans addressing the following:
a. Correct the lot area size. According to the assessor's maps the lot size is 51,223 square feet. Please adjust the lot coverage accordingly.
b. Add all the dimensions on the elevation sheet.

If you have any questions about this transmittal, please contact me at Nicholas.Martell@tucsonaz.gov
05/04/2021 PCAMARE1 ENGINEERING REVIEW Reqs Change FROM: Paul Camarena
PDSD Engineering Review Section

PROJECT: T21CM03254
5001 N WILD LIFE DR


TRANSMITTAL DATE: April 21, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Engineering Review Section comments were addressed.

01. COMMENT: Engineering has reviewed the plan and cannot approve at this time. Please address the following comments.

02. COMMENT: This project is located in the Hillside development zone a grading development package is required. The grading plan needs to include but not limited to the: top and toe of slopes, pad elevation, show area that can be developed, show natural undisturbed open space.


03. COMMENT: Engineering cannot approve the building plan until the Grading Development Package is approved.



If you have any questions about this transmittal, Contact Paul Camarena at Paul.Camarena@tucsonaz.gov
05/04/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM03254
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL COMMENTS:

1. When the clothes washer is not near an exterior wall show a gray water bathing fixture drain looped 3’ beyond an exterior wall below grade before connection to the building drain. See details at https://www.tucsonaz.gov/files/pdsd/codes-ordinances/Grey_Water_Options_FINAL_.pdf

SITE PLAN:

1. Indicate the location of buildings, utility meters and gas, water, electric and sewer or septic lines from property line to building, R106.1.1. Show the point of connection of proposed lines to the utility service for verifying correct sizes and necessary upgrades.

SECTIONS - DETAILS:

1. An attic (space between roof and insulation) requires a calculation for showing the attic ventilation opening size using 1 to 150 of attic area in compliance with R806.2. Provide appropriate upper and lower space vents when applying the reduced area calculation. Account for the existing attic space if removing or blocking existing vents.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans.

Please contact the plans reviewer if you have any questions:
Ken Van Karsen
(520) 837-4912 PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review
05/10/2021 AWARNER1 NPPO REVIEW Reqs Change CDRC TRANSMITTAL

TO: Planning and Development Services Department, Plans Coordination
FROM: Anne Warner, RLA
PDSD Landscape/NPPO Review
PROJECT: 5001 N. Wild Life Ave, new single-family residentce
T21CM03254

TRANSMITTAL DATE: May 10, 2021
DUE DATE: May 13, 2021

7.7. Native Plant Preservation
An approved Native Plant Preservation Plan Sections 7.7.4 is required or a request for an exception from the Native Plant Preservation requirements in accordance with Sections 7.7.3.D.3 & .4 of the Unified Development Code (UDC) is required prior to Grading Plan approval.

If you have any questions about this transmittal, Contact Anne Warner at (520) 837-4969 or by email anne.warner@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: NPPO Plan or NPPO Exception request
05/14/2021 JVINCEN1 FIRE REVIEW Reqs Change This residence will have a “fire-flow calculation area”(2018 IFC Appendix B, Section B102 and 105.1) greater than 3,600 sq. ft.: therefore this house will require a residential sprinkler system unless the fire flow in the nearest hydrant is a minimum of 1,750 GPM for 2 hours duration at 20 psi residual pressure. Additionally, the hydrant must be within 600’ of all parts of the residence. Contact Tucson Water engineering for a hydraulic analysis. Provide notes on plan regarding verification of fire flow and proximity of hydrant or intent to install a fire sprinkler system. If a system will be installed, residential or quick response sprinklers shall be used. The sprinkler system may be connected to the domestic water supply, provided the required design density can be met. Be advised that Tucson Water will not allow a residential sprinkler system to be supplied by a 5/8" meter. A minimum of ¾” meter will be required by Tucson Water. Residential fire sprinkler system shall be installed in accordance with the 2018 IFC and NFPA 13D.