Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T21CM03225
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/29/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 05/06/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A.1; Plans: Please provide a north arrow on all plans. 2. Sheet A.1; Elevations 4 and 5: Please verify Elevation 4 is the West Elevation and Elevation 5 is the North Elevation. 3. Sheet A.1: Please provide a Code Analysis on this sheet for the storage room addition. Include the addition SF, Construction Type, Occupant Load, and Occupancy Classification. 4. Sheet S1.3; Detail 14: Please provide on this detail the vertical dimension ("H") of the lintel plate. 5. General: Please provide a Special Inspections Certificate with Parts A and B completed. Include epoxy anchors, expansion anchors, and masonry construction. 6. General: Please provide written responses to all review comments. |
| 05/11/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 05/11/2021 | SSHIELD1 | ENGINEERING | REVIEW | Reqs Change | SEE ZONING COMMENTS |
| 05/11/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM03225 4855 E Broadway Blvd Storage Addition TRANSMITTAL: May 11, 2021 This site is located in the O-3/C-1 zone (UDC O-3 4.7.15/C-1 4.7.20). 1. As you are proposing an addition to an existing commercial building a development package is required. Submit a development package that at a minimum meets the requirement of the checklist for Minor Changes to Commercial/Industrial sites found at: https://www.tucsonaz.gov/files/pdsd/forms/Minor_Changes_to_Commercial_Industrial_Sites_.pdf. If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/11/2021 | IMONSHI1 | OUT TO CUSTOMER | Completed |