Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T21CM03164
Parcel: 128113750

Address:
4833 E COOPER ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM03164
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/16/2021 SBLOOD1 ENGINEERING REVIEW Passed
05/03/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T21CM03164
4833 E Cooper St
Attached Front Porch (1st Review)

TRANSMITTAL DATE: May 03, 2021

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 - .9.

1. Provide a residential plot plan that meets all requirements shown on the residential plot plan requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf. Specifically the plot plan shall provide street and interior perimeter yard setback dimensions and the distance from centerline of street to curb and property line. The distance from centerline of the street to the face of curb, where pavement meets the concrete curb, is 16’ and from face of curb to property line is 9’. The required street perimeter yard is 20’ or 1-1/2 the height of the proposed exterior wall, in this case it is the height measured from design grade to the top of beam supporting the roof rafters.

2. Provide a height dimension from design grade to the top of beam supporting the roof rafters.

3. The drawing plans shall be submitted as a single multi-page pdf file.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov
05/03/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits
FOUNDATION PLAN:
1. Dimension the footing length, width, and depth into undisturbed soil for each footing type and condition, R403.1.1.

FRAMING PLAN:
1. Provide a complete roof framing plan with beams and rafters sized with appropriate load carrying capacity, R301.1.

SECTIONS - DETAILS:
1. Show the Post Section Detail with the footing, R403.1.
2. Notate and specify the size and length of anchor bolts, R403.1.
3. Show roof (uplift resistance) fasteners (H2.5) with appropriate uplift capacity, R802.11 amended.
4. Show connection at dwelling with fasteners (rafter on top plate with H2.5 or ledger with rafter hangers).

Please contact the plans reviewer if you have any questions:
Ken Van Karsen
PDSD-Residential@tucsonaz.gov
05/03/2021 SSHIELD1 NPPO REVIEW Passed