| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/27/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 04/28/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 04/30/2021 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T21CM03114 GENERAL: o Provide written responses to all review comments. o Provide a complete plan set. o Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: NA BUILDING REVIEW COMMENTS: Approved ELECTRICAL REVIEW COMMENTS Denied E1: No electrical issues E2: No electrical issues E3: Is doorway on Northeast plan next to doctor's office an exit? Add exit sign if required. E4: No electrical issues E5: No electrical issues E6: No electrical issues E7: No electrical issues MECHANICAL REVIEW COMMENTS: Denied 1. Show existing or new roof top opening construction support details per 2018 IMC 301.15. 2. Provide rooftop equipment piping construction attachment details per 2018 IMC 310.15. 3. Show refrigeration coolant systems classification types and locations per 2018 IMC 1103. 4. Provide duct work and exhaust piping support spacing information per 2018 IMC 603.10. 5. Show new rooftop mechanical units convenience receptacle location per 2017 NEC 210.64. 6. Provide new rooftop equipment curb installation construction details per 2018 IBC 1604.1. 7. Show commercial dryer roof top vent curb and construction details per 2018 IMC 302.1. PLUMBING REVIEW COMMENTS: NA |
| 05/05/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 05/05/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 05/05/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed |