Permit Number: T21CM03112
Parcel: Unknown

Address:
3829 N ORACLE RD

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T21CM03112
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/10/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
05/10/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Verify that the mechanical design does not use the corridor as a return air duct (i.e. there is a supply and return in each room). Reference: Section 601.2, IMC 2018. [Initial comment: This appears to be a change of use. Provide a code analysis and determine the ventilation requirements.]
05/10/2021 ROBERT SHERRY WATER REVIEW Completed
05/14/2021 JVINCEN1 FIRE REVIEW Approved
05/26/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Passed No electrical work in the scope.
06/03/2021 STEVE SHIELDS ZONING REVIEW Approved