Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM03112
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/14/2021 | JPEELDA1 | FIRE | REVIEW | Reqs Change | This is a change of use. This plan set will require: 1) Code Annalysis 2) Clear site plan 3) change/ addition of interior walls 4) Wall detains 5) mechanical changes if they were made 6) Plumbing changes if they were made 7) Electrical changes if they were made Fire will also need to know if there is a fire sprinkler and or fire alarm permit. Jennifer.Peel-Davis@Tucsonaz.gov 520-837-7033 |
| 04/15/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | This appears to be a change of use. Provide a code analysis and determine the required number and types of plumbing fixtures. |
| 04/15/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | This appears to be a change of use. Provide a code analysis and determine the ventilation requirements. |
| 04/15/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 04/27/2021 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 04/27/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Floor Plan: Please include a Code Analysis on this sheet, indicating the Square Footage, the Occupancy Classification, the Construction Type, if there is an automatic sprinkler system, and the Occupant Load. In addition, please provide plumbing fixture calculations per the IBC Table 2902.1. 2. Floor Plan: Please indicate the new walls and the construction of those walls (stud size, spacing, gypsum board, etc.). In addition, indicate the wall bracing at the top of the wall to meet the load requirements of the IBC Section 1607.15. 3. Site Plan: Please indicate the location of this project on the Site Plan. The plan is very difficult to read. 4. General: Please provide written responses to all review comments. |
| 05/04/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 05/10/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 05/10/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM03112 3829 N Oracle Rd Use Unknown TRANSMITTAL: May 10, 2021 This site is located in the C-2/I-1 zone (UDC 4.7.27). 1. Provide the proposed use on the plans. If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov. |